CONTROLS

EN SERIES

LIQUID LEVEL CONTROL

UL listed CSA recognized
• Pump Up or Down Control
• DIN-Rail Enclosure
• 5 to 100
• SPDT 8 Amp Relay Output

CONTROLS

GENERAL FEATURES:

The EN series is designed to monitor conductive liquids such as tap water, waste water, sea water, coffee, etc. The principle is based on the measurement of the resistance of the liquid between two submerged probes. When this value is lower than the preset threshold selected on the dial of the unit, the output relay changes state. Applications are found in the environmental and chemical industries, food equipment machinery and food processing technology.

SPECIFICATIONS:

Input Power 24, 110, 230 VAC +15% 50/60 Hz

Max. Power Consumption 3 VA Probe Sensitivity 5 to 100 Probe Voltage 24 VAC Max. Probe Current 5 mA Max. Probe Cable Capacitance 10 nf Probe/Output Relay Insulation 2,500 k VAC Output Relay SPDT Relay Max. Output Rating 8 Amp Relay Electrical Life 2 x Operating Temperature +14°F to 140°F -20°C to 60°C Weight 5 oz. 140g

CONFORMITY:

Immunity to interference and noise EMC IEC Surge immunity Level 3 IEC Electrostatic discharges Level 3 IEC Damped oscillated waves Level 3 IEC Radiated disturbance Level 3 IEC Fast transient Level 3 IEC Conducted RF Level 3 ENV 50141

RF Emissions EMC CENELAC EN 55022 Class A

FILLING OR EMPTYING CONTROL EN :

Maximum level Minimum level

Output relay

Down or Up

Unit power-up

Controlled level

Emptying function Filling function

Power U

Controlled Level

Output relay

Down or Up

Unit power-up

Controlled level Draining function Filling function

Regulation of two levels Minimum / Maximum

The output relay changes state when the level of liquid reaches the maximum electrode, with the minimum electrode submerged. It returns to its initial state when the minimum probe is no longer in contact with the liquid.

Regulation of one level:

Connect the maximum and common terminals together. The relay will change state when the minimum probe enters or leaves the liquid.

Note If the power break lasts for seconds or more, the relay reenergizes instantly if in mode and is deenergised if in mode.

WIRING:
ORDERING INFORMATION:

Voltage 24 VAC 24 VAC 120 VAC 120 VAC 230 VAC 230 VAC

Part Number 84 870 001 84 870 101 84 870 003 84 870 103 84 870 004 84 870 104

Type EN, Pump Up/Pump Down Selectable END, Pump Down Only EN, Pump Up/Pump Down Selectable END, Pump Down Only EN, Pump Up/Pump Down Selectable END, Pump Down Only

A1 11

C min max
12 14

Products and specifications subject to change without notice.

Consult factory for application assistance.
204 Airline Drive, Suite 300, Coppell, Texas 75019 / Tel 800 677-5311 / FAX 800 677-3865 / 5-4
More datasheets: AS1539-BTST | AS1539-BTSU | AS1541-BQFT | 264-10SURD/S530-A3 | FMS7G10US60S | 834000T00000 | AOD472A | FDS9412 | FQI11P06TU | 84870004


Notice: we do not provide any warranties that information, datasheets, application notes, circuit diagrams, or software stored on this website are up-to-date or error free. The archived 84870101 Datasheet file may be downloaded here without warranties.

Datasheet ID: 84870101 507162