Datas hee t - CP8 4 1 A Con tr ol l er

Galaxy Pulsar Edge Controller for Compact Power Line Applications

The Compact Power Line Galaxy Pulsar Edge controller delivers large system intelligence in a small form factor. The Pulsar Edge is a family of controllers that function as a network interface controller NIC and as a fullfeatured power system controller for the J2007001 family of Compact Power Line CPL shelves. Its thin modular plug-in form factor minimizes shelf space consumption allowing maximum power module and distribution capabilities providing a feature set found in controllers used in larger power systems ranging up to 20k amps. The CP841A controller is specific member of the Galaxy Pulsar Edge family.

The Pulsar Edge CP841A controller is utilized in bulk power applications in data centers and enterprise applications. Ethernet connectivity with SNMP facilitates remote network management access through its frontaccessible RS232 and is aided by the EasyView2 graphical user interface as well as a web interface.

As a battery plant controller, it provides a complete set of features over a half-duplex RS485 bus to monitor and control rectifiers, batteries, and distribution. A flexible set of configurable inputs allow the CP841A to monitor a wide variety of system equipment and incorporate appropriate state information enabling a centralized point of management.

The controller utilizes standard network management protocols allowing for advanced network supervision from standard. GE Critical Power Galaxy Manager software is the centralized visibility and control component of a comprehensive power management system designed to meet engineering, operations, and maintenance needs. The Galaxy Manager client-server architecture enables remote access to system controllers across the power network.
• Enterprise Networks - Voice, Data, PoE
• Telecommunications networks
• Transmission equipment
• Fiber in the loop
• Routers/switches
• Data networks
• PBX

Key Features

Remote Access and Features
• Integrated 10/100Base-T Ethernet Network - TCP/IP - SNMP V3 for management - SMTP for email - Telnet for command line interface - DHCP for plug-n-play - for rapid backup and upgrades - for standard web pages and browsers - Compatible with Galaxy Manager and other management packages - Shielded RJ-45 interface referenced to chassis ground
• Password protected security levels User, Super-User, Administrator for all access
• Ground-referenced RS232 system port
• ANSI T1.317 command-line interface
• Modem access support - Remote via external modem - Callback security
• EasyView2, Windows-based GUI software for local terminal or Modem access
• Supporting the following Protocols:
- SNMP V3
- SSL
- SSH

Standard System Features
• Monitor and control of more than 40 connected devices - Maximum of 32 rectifiers - Maximum of 6 distribution control cards - Robust RS485 system bus
• Standard and user defined system alarms - Alarm test - Assignable alarm severity Critical, Major, Minor, Warning, and Record-only
• Rectifier management features - Automatic rectifier restart - Active Rectifier Management energy efficiency - Remote rectifier on/off - Reserve Operation - Automatic rectifier sequence control - N + X redundancy check
• Multiple Low Voltage Load and Low Voltage Battery Disconnect thresholds 4
• Configuration, statistics, and history - All stored in non-volatile memory - Remote/local backup and restore of configuration data
• Industry standard defaults - Customer specific configurations available
• Remote/ local software upgrade
• Basic, busy hour, and trend statistics
• Detailed event history
• User defined events and derived channels
08/13 Galaxy Pulsar Edge Controller, CPDS-EDGE 2013 General Electric Company. All rights reserved.

Standard Battery Management Features
• Float/boost mode control
- Manual boost - Manual timed boost locally, T1.317,
and remotely initiated - Auto boost terminated by time or current
• Battery discharge testing - Manual local/remote - Periodic - Plant Battery Test PBT input driven - Configurable threshold or
20% algorithm - Graphical discharge data - Rectifiers on-line during test
• Slope thermal compensation - High temperature - Low temperature - Step temperature - STC Enable/Disable, low temperature

Enable/Disable - Configurable mV/°C slopes
• State of charge indication
• High temperature disconnect setting
• Reserve-time prediction
• Recharge current limit
• Emergency Power-Off input

Datas hee t - CP8 4 1 A Con tr ol l er

Integrated Monitoring Inputs/Outputs
• System plant voltage accuracy resolution 0.01V
Ordering Information
Ordering Code CC109145331 150032047

Model CP841A_3C3R CP841A_3C3R_S

Galaxy Pulsar Edge Controller

Galaxy Pulsar Edge Controller with Security Features Update

Contact Us

For more information, call us toll free at +1 877 546 3243, or +1 972 244 9288 and visit us on the web at
08/13 Galaxy Pulsar Edge Controller, CPDS-EDGE 2013 General Electric Company. All rights reserved.
More datasheets: KSC838YTA | KSC838CYBU | KSC838OBU | KSC838YBU | KSC838OTA | DCMMN8H8PNA101 | BF888H6327XTSA1 | CA3106F24A24PB14F0 | SDP8304-301 | SDP8314-301


Notice: we do not provide any warranties that information, datasheets, application notes, circuit diagrams, or software stored on this website are up-to-date or error free. The archived 150032047 Datasheet file may be downloaded here without warranties.

Datasheet ID: 150032047 645622