MVU14-10FLK

MVU14-10FLK Datasheet


MVU18-4FL thru MVU10-14FL

Part Datasheet
MVU14-10FLK MVU14-10FLK MVU14-10FLK (pdf)
Related Parts Information
MVU14-14FLK MVU14-14FLK MVU14-14FLK
MVU14-4FLK MVU14-4FLK MVU14-4FLK
MVU10-6FLK MVU10-6FLK MVU10-6FLK
MVU14-6FLK MVU14-6FLK MVU14-6FLK
MVU14-8FLK MVU14-8FLK MVU14-8FLK
MVU10-14FLK MVU10-14FLK MVU10-14FLK
MVU10-8FLK MVU10-8FLK MVU10-8FLK
MVU10-10FLK MVU10-10FLK MVU10-10FLK
PDF Datasheet Preview
Scotchlok Terminals

MVU18-4FL thru MVU10-14FL

Locking Fork, Vinyl Insulated, Butted Seam

Data Sheet

Wire

Maximum

Product Range Stud Lock

Barrel Insulation

Number AWG Size Width W

E Thickness Length I.D. Diameter

MVU18-4FL 22-18 4

MVU18-6FL 22-18 6

MVU18-8FL 22-18 8

MVU18-10FL 22-18 10

MVU14-4FL 16-14 4

MVU14-6FL 16-14 6

MVU14-8FL 16-14 8

MVU14-10FL 16-14 10

MVU14-14FL 16-14 1/4

MVU10-6FL 12-10 6

MVU10-8FL 12-10 8

MVU10-10FL 12-10

MVU10-14FL 12-10 1/4

Installation Information

LISTED 314R

UNDERWRITERS LABORATORIES STANDARD NO. UL 486A 3M FILE NO. E23438

CANADIAN STANDARDS ASSOCIATION STANDARD NO. C22.2 NO. 65 3M FILE NO. LR22190

Specifications

Wire Size Barrel Seam Max. Voltage Rating:

Max. Temperature Rating Max. Current Insulator Material Terminal Material Plating:

See Table Above Butted 600 V Building Wire 1000 V Signs, Fixtures and Luminaires Same as Wire Vinyl ETP Copper Tin

WARNING

Turn power off before installing or removing terminal. All electrical work should be done according to appropriate electrical codes.

UL Listed and CSA Certified for use on stranded copper AWG wire only. Strip away the end 3/8 inch of wire insulation. Make the crimp in the proper station of a recommended 3M crimp tool TH-440, TH-450 scissor style , or TR-490 ratchet style hand tools.

Barrel Crimp Electrical

Engineering Specification

Crimp-type terminals shall, electrically and mechanically, connect to a pre-stripped end of a stranded copper wire and have a flat tongue portion with a central opening for mounting around a screw or stud.

The terminal line shall offer tongue variations in hole stud size 6, 8 10, etc. and configuration ring, fork, block fork, flanged block fork, locking fork, etc. and barrel variations in wire AWG size 22-18, 16-14, 12-10, etc. and construction non-insulated brazed seam, vinyl insulated butted seam, nylon insulated with insulation grip, etc. . The terminal line shall have regulatory agency coverage UL Listing, CSA Certification . The terminal tongue shall be marked with the wire range and manufacturer’s symbol

The vinyl-insulated, butted seam locking fork terminal shall be tin-plated, annealed copper, with the tongue having a specified stud slot size 4 thru 1/4 in. and a butted seam barrel covered by a molded vinyl funnel entry sleeve, color coded and sized, for a specified AWG wire range 22-18, 16-14,

Insulated terminals shall be UL Listed and CSA Certified for 600 Volts maximum building wire 1000 Volts maximum in signs, fixtures and luminaries and have a maximum operating temperature of 221°F 105°C .
3M and Scotchlok are trademarks of 3M
More datasheets: DM74AS244SJ | DM74AS244SJX | DM74AS240WMX | AK93C41AV | MVU14-14FLK | MVU14-4FLK | MVU10-6FLK | MVU14-6FLK | MVU14-8FLK | MVU10-14FLK


Notice: we do not provide any warranties that information, datasheets, application notes, circuit diagrams, or software stored on this website are up-to-date or error free. The archived MVU14-10FLK Datasheet file may be downloaded here without warranties.

Datasheet ID: MVU14-10FLK 520960