GEM600-24G

GEM600-24G Datasheet


GEM600

Part Datasheet
GEM600-24G GEM600-24G GEM600-24G (pdf)
PDF Datasheet Preview
GEM600
600W Single Output Economy/Technology Switchers

Commercial and Medical
2 Year Warranty
•600W Single Output AC-DC Power Supply
•Universal Input 90-264 VAC
•Standard Active PFC, OVP, Power Fail and Inhibit low
•Modified and Customized Designs also available
•Complies with EMI/RFI Standards
•Approved to EN/IEC/UL/CSA 60950-1 for ITE
•Approved to EN/IEC/UL60601-1 for Medical

Compliant LVD, RoHS

Specifications

All Specifications are typical at nominal input, full load at 25°C unless otherwise stated.

AC Input 90-264VAC, 47-63 Hz single phase.

Input Current 120VAC 9A, 230VAC 4.5A.

Inrush Current Limited by internal thermistor. The inrush at 240VAC, averaged over the first AC half-cycle under cold start conditions will not exceed 40A.

Input Fuse F1, F2 12A, 250VAC fuses provided on all models.

Power Factor typical, minimum.

Earth Leakage Current 120VAC 75µA max. NC, 120µA max. SFC. 264VAC 160µA max. NC, 300µA max. SFC.

Output Power 600W continuous.

Peak Output Power 650W for 1 minute, 10% duty cycle.

Output Voltage See chart.

Voltage Adjustability Adjustable potentiometer, capable of ±5% change from nominal.

Minimum Load Not required.

Total Regulation See chart.

Transient Response 500µs max., 50% load step, < 0.2A/µs.

Enclosure Dimensions See outline drawing

Turn On Time Less than 2 seconds under all rated load conditions.

Hold-up Time ms from loss of AC input at 600W load, 120VAC input. Over/Undershoot max. at turn-on, 1% max. at turn-off.

Output Overload & Short Circuit Protection

Foldback, then cycle-by-cycle current limiting, automatic recovery.

Overvoltage Protection

Latching type, recycle AC input to reset. See chart for trip levels.

Ripple and Noise
1% pk-pk max., 20MHz BW, differential mode. Measured with noise
probe directly across output terminals.

ITE Safety Standards

CSA/EN/IEC/UL 60950-1

Medical Safety Standards

EN/IEC/UL 60601-1

Efficiency
>80% typical at full rated load

Switching Frequency
140KHz main inverter and 70kHz PFC synchronized .

MTBF
208K hours per Telcordia.
More datasheets: KX0607 | KX0606 | CR0028 | CR0060 | A-PC2304-020028-1 | W2E143-AA15-01 | 3661 | U4285BM-MFS | U4285BM-MFSG3 | 96SW-SER16STD-EN


Notice: we do not provide any warranties that information, datasheets, application notes, circuit diagrams, or software stored on this website are up-to-date or error free. The archived GEM600-24G Datasheet file may be downloaded here without warranties.

Datasheet ID: GEM600-24G 506298