GE Critical Power

Quick Start Guide

CP Converter Shelf System

Shelf J2007001 L014 CC109157657

DC input from left and right

L015 150042727

DC input from left only

Converters CP2000DC54PEZ CC109162104

CP2500DC54PEZ CC109170528

Controller CP841_3C3R

CC109145331

No vertical spacing is required, allow a minimum 2 inch clearance at back of shelf for rectifier airflow. Refer to Compact Power Line CPL Brochure for details and accessories.

Tools required:

Wire cutters and strippers Cable crimpers

Torque wrench - 0-65 in-lb 0-10Nm Sockets - 5/16”, 7/16, etc.

Screwdrivers - Philips #1 and #2, Flat small

Step 1 - Mount Shelf

Reposition mounting ears as required - 8 screws each. Torque to 25 in-lb 2.8Nm - Phillips screwdriver.

Attach shelf to the frame using a minimum of four screws two on each side - 12-24 provided . Torque to 35 in-lb 4Nm - 5/16” socket.

Step 3 - Connect -48V Output and Output Return

Lugs - 1/4” on 5/8” centers not provided . Torque to 65 in-lb Nm - 7/16” socket.

Step 4 - Connect DC Inputs
• Feed each input from 80A breaker shelf rating limited

Step 2 - Connect Chassis Ground

Some applications may rely on frame mounting screws for shelf ground omitting the chassis ground cable.

Minimum 6 AWG wire is recommended. Lugs - 1/4” on 5/8” centers not provided .

Torque to 65 in-lb Nm - 7/16” socket.

Lugs - 1/4” on 5/8” centers not provided . Torque to 65 in-lb Nm - 7/16” socket

CAUTION Verify DC Input voltage and polarity with a voltmeter before proceeding.

Note Input Feed Returns must be externally connected to DC Reference CO ground.

Output Return Ground
-48V Output

DC Inputs - Converter Inputs
4 3 POS NEG

NEG POS

Chassis Ground

L014 shown L015 has all DC input feeds from the right as viewed from the rear

CP Converter Shelf - Quick Start Guide Document 850033106 r04 2015 April

J4 1-Wire Battery Temp and Voltage Monitor

J1 Alarms and Inputs - page 4

J5 LAN Port J2 External Alarm Inputs - page 4

RS-232 Craft port
• Specifications and ordering information are in the Compact Power Line CPL Brochure available at
• Equipment and subassembly ports are suitable for connection to intra-building or unexposed wiring or cabling;
can be connected to shielded intra-building cabling grounded at both ends.
• Grounding / Bonding Network Connect to an Isolated Ground Plane Isolated Bonding Network or an Integrated Ground Plane Mesh-

Bonding Network or Common Bonding Network .
• Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies.
• DC return may be either Isolated DC return DC-I or Common DC return DC-C .

Reference Documents

These documents are available at

Document 850035894 CC848836981

Title Galaxy Pulsar Edge Quick Start Guide Galaxy Pulsar Edge Controller Family Product Manual Compact Power Line CPL Brochure