CONTROLS

FW SERIES

PHASE CONTROL RELAY

UL cUL listed CSA recognized
•Monitors and Protects Against
•Rugged Construction for Over Voltage and Transient Protection

CONTROLS

GENERAL FEATURES:

OPERATING PRINCIPLE:

The unit has two front dial settings. The upper dial is used for the

In a 3-phase network, the FW simultaneously monitors phase
three phase nominal voltage settings that exists in the application.
sequencing, loss of phase with a maximum regeneration rate

The lower dial setting is for an adjustable time delay to prevent nuisance tripping of the unit. The FW has a space saving 45mm wide DIN-rail mount/surface mount enclosure and LED power-on and relay status indication.
of 70% of the displayed by a potentiometer on the front face, and the voltage drop on the 3 phases of less than 15% of the preset value. When the 3 phases suceed one another, the output relay is activated and indicated via a yellow LED. The output relay de-energizes LED off after a time delay T,

SPECIFICATIONS:

Model No.
84873010
84873011
84873015 84873016
adjustable between and 10 seconds on the front face, if one of the following faults is present :

Input Power
3 x 230VAC 3 x 380VAC 3 x 480VAC 3 x 600VAC

Threshold Adjustment 184 - 264VAC 310 - 337VAC 384 - 552VAC 460 - 661VAC

Maximum Voltage
264VAC
337VAC
552VAC 661VAC
- absence of one or more phases - voltage drop

Minimum Voltage Frequency
184VAC 50/60 Hz
304VAC 50/60 Hz
384VAC 460VAC 50/60 Hz 50/60 Hz

CONFORMITY:

Max. Power Consumption 6 VA [Powered from L1 & L2] Immunity from micro power cuts 10 ms

Immunity to interference and noise EMC IEC Surge immunity Level 3

Delay on pick-up 500 ms

IEC Electrostatic discharges Level 3

Isolation coordination Category III Degree of pollution 2 acc. to IEC 664-1 VDE 0110 4 KV/2

IEC Damped oscillated waves Level 3 IEC Radiated disturbance Level 3 IEC Fast transient Level 3

Measurement input resistance 1 x input power
ORDERING INFORMATION:

Voltage
3 x 230 VAC 3 x 380 VAC 3 x 480 VAC 3 x 600 VAC
84873010 84873011 84873015 84873016

Products and specifications subject to change without notice.

Consult factory for application assistance.
95 100
204 Airline Drive, Suite 300, Coppell, Texas 75019 / Tel 800 677-5311 / FAX 800 677-3865 / 5-13
More datasheets: AT34C02-10PI-2.7 | AT34C02-10TI-1.8 | AT34C02-10TI-2.7 | AT34C02N-10SI-2.7 | AT34C02N-10SI-1.8 | AT34C02Y1-10YI-1.8 | AT34C02Y1-10YI-2.7 | AT34C02-10TU-1.8 | 84873011 | 84873016


Notice: we do not provide any warranties that information, datasheets, application notes, circuit diagrams, or software stored on this website are up-to-date or error free. The archived 84873015 Datasheet file may be downloaded here without warranties.

Datasheet ID: 84873015 507090