GLC75 Commercial/GLM75 Medical 75 Watt Single Output Global Performance Switchers

SPECIFICATIONS:

Ac Input 90-264 Vac, 47-63 Hz single phase.

Input Current Maximum input current at 120 Vac, 60 Hz with full rated output load not to exceed A.

Output Power Normal continuous output power is 75 W for unrestricted natural convection cooling 110 W with 26 cfm airflow.

Output Regulation measured by changing from 5% to 50% load or 50% load to full load in either direction.

Overload Protection Factory set to begin power limiting at approximately 120 W GLC 75-5 is set at approximately 100 W . Fully protected against short circuit and output overload. Short circuit protection is cycling type power limit.

Output Noise rms, 1% pk-pk, 20 MHz bandwidth, differential mode. Measured with noise probe directly across output terminals of the power supply.

Transient Response Main Output 500 µs typical response time for return to within of final value for a 50% load step change, A/µs. Maximum voltage deviation is Startup/ shutdown overshoot less than

Overvoltage Protection Standard on all models.

Voltage Adjust Factory set on standard unit however, potentiometer adjusts voltage ±5% minimum. Consult factory for application assistance.

Efficiency 72-85% depending on model.

Input Protection Internal ac fuse provided. Designed to blow only if a catastrophic failure occurs in the does not blow on overload or short circuit.

FEATURES:
• Cost-effective single-output power source
• x meets 1U applications
• Universal input 90-264 Vac
• 2-year warranty
• Complies with EN61000-3-2 Class A
• Also available in multiple output versions
• Conducted EMI exceeds FCC Class B and CISPR 22 Class B Commercial models and CISPR 11 Class B Medical models
• Commercial Approved to UL1950, CSA22.2 No. 234 and IEC950, EN60950
• Medical Approved to UL2601-1, IEC601-1 and CSA22.2 No. 601
marked to LVD

Inrush Current Inrush limited by internal thermistors. Inrush at 240 Vac, averaged over the first ac half-cycle under cold start conditions will not exceed 37 A.

Temperature Coefficient 0.03%/°C typical on all outputs.

Power Fail A standard TTL or CMOS compatible output goes low < V 5ms before output voltage drops more than 4% below nominal voltage upon loss of ac power. Signal is factory set to trip on 84 to 94 Vac brown-out depending upon incoming line impedance and distortion. Other settings are available through adjustment of built-in potentiometer consult factory for assistance . Output will stay low for 20 ms minimum.

EMI/EMC Compliance

All models include built-in EMI filtering to meet the
following emissions requirements:

EMI SPECIFICATIONS

COMPLIANCE LEVEL

Conducted Emissions GLC75 EN55022 Class B FCC Class B

Conducted Emissions GLM75 EN55011 Class B FCC Class B

Static Discharge

EN61000-4-2, 6 kV contact, 8 kV air

RF Field Susceptibility

EN61000-4-3, 3 V/meter

Fast Transients/Bursts

EN61000-4-4, 2 kV, 5 kHz

Surge Susceptibility