D0900.0010

D0900.0010 Datasheet


D0100 series & D0900 series

Part Datasheet
D0900.0010 D0900.0010 D0900.0010 (pdf)
Related Parts Information
D0100.0010 D0100.0010 D0100.0010
D0100.0020 D0100.0020 D0100.0020
PDF Datasheet Preview
Protection Relays & Controls

Arc-Flash Monitoring

D0100 series & D0900 series

Arc-Flash Relay

Installation Diagram

Place sensors in direct line of sight to possible arc faults, preferably pointing down from the ceiling.
Ordering Information
Ordering Number

D0100.0010 D0100.0020 D0900.0010

Control power
48-220 Vdc 24 Vdc 220-250 Vac
accessories

A0033.0010 Detector cable 2 x mm w/screen. 100 m

A0200.0010 Light Sensor 5 m cable

A0200.0020 Light Sensor 10 m cable

A0200.0030 Light Sensor 15 m cable

A0300.0010 Light Sensor 5 m cable

A0300.0020 Light Sensor 10 m cable

A0300.0030 Light Sensor 15 m cable D0400.0010 Junction Box. For 8 sensors, without indication D0500.0010 Junction Box. For 8 sensors, with indication
requirement Optional

Required At least 1 sensor per cubicle or drawer

Optional

D1100.0010 Diode Logic Unit

Optional
2013 Littelfuse Protection Relays & Controls Littelfuse.com/d0900

The D0100/D0900 Arc-Flash relays provide a simple and costeffective solution for Arc-Flash monitoring. Two light sensors can be connected directly to one relay, or optional junction boxes allow up to 16 sensors per relay.

Light Sensors react to light and are available with 180º or 360º detection area. Sensors are supplied with 5, 10 or 15 m of cable and a mounting bracket. 1-2 sensors are recommended per cubicle or drawer.

Compact module Fits into wide range of Arc-Flash applications

Trip time <1 ms Limits Arc-Flash damage and risk of injury

Two optical sensor types Dual sensor input Sensor expansion option

Point sensors with 180° or 360° detection area depending on specific installation

Single Arc-Flash relay can monitor 2 sensors or junction boxes

Junction box allows for up to 16 sensors per Arc-Flash relay 8 sensors/box

Adjustable light Allows for operation in bright environments and
sensitivity
maximum sensitivity in dark environments

Service mode

Allows for system test without tripping

Accessories

A0200 Light Sensors

Line-of-sight light sensor detects an arc as small
as 3 kA within a 2-m half-sphere. Available in
or 5, 10, or 15 m cable.

D0400/D0500 Junction Box for parallel connection of more than 2 sensors for one relay. Designed to connect up to 8 sensors, and is available with and without indication. Max. 2 junction boxes can be connected to one Arc-Flash relay.

Specifications

Voltage Supply

D0100.0010 48-220 Vdc

D0100.0020 24 Vdc
More datasheets: 1510 | 1503 | SPB204 EVK | DBM13W3PA190 | DCMMV21HA4PNA101 | USB-ICP-SAB9 | MIKROE-2814 | MIKROE-2811 | MDSM-9SC-Z11-VS1 | D0100.0010