B85321-A2405-A630

B85321-A2405-A630 Datasheet


B85321 May 2014

Part Datasheet
B85321-A2405-A630 B85321-A2405-A630 B85321-A2405-A630 (pdf)
PDF Datasheet Preview
EMC filters

Feedthrough components Filters

Series/Type Date:

B85321 May 2014

EPCOS AG Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without EPCOS' prior express consent is prohibited.

EPCOS AG is a TDK Group Company.

Feedthrough components Filters

Rated voltage VR 250 V AC Rated current IR 16 A to 500 A Rated capacitance CR 2 x µF to 2 x µF

Construction Building-block system MKP technology dry, self-healing Dielectric polypropylene, metallized Metal case, polyurethane potting UL 94 V-0 For central screw fixing

Features Compact dimensions Versions with rated voltage 440 V AC available on request High insertion loss Easy to install High contact reliability thanks to central screw fixing Comply with IEC 60939 UL and cUL approvals

Typical applications Broadband interference suppression for AC/DC supply lines, e. g. in
shielded rooms telephone exchanges, base stations electrical machines and systems power supplies

Terminals Threaded studs Axial leads Soldering tag Tab connectors
Marking on component Manufacturer's logo, ordering code, rated capacitance, rated voltage, rated current, climatic category, circuit diagram, date code, approvals
Minimum data on packaging Manufacturer's logo, ordering code, quantity, date code

Circuit diagram

Please read Cautions and warnings and Important notes at the end of this document.

Page 2 of 12

B85321

Feedthrough components Filters

B85321A*160 16 mm, 16 A

Feedthrough filters 16 mm Technical data and measuring conditions

Rated voltage VR Rated current IR

Capacitance tolerance Climatic category IEC 60068-1 Screw cap fixing Approvals
250 V AC 50/60 Hz / 600 V DC Referred to 40 °C rated temperature Reduced current values at 400 Hz ±20% 40/085/56 °C/+85 °C/56 days damp heat test M10 x UL 1283, 250 V AC and CSA C22.2 No.8, 250 V AC
Characteristics and ordering codes

IR CR A µF

Terminal

Figure Approx. weight g

VR = 250 V AC, VR = 600 V DC, Vtest = 2700 V DC
16 2 x M2
16 2 x Soldering tag 2
16 2 x Axial leads
16 2 x Tab connectors 4
Ordering code

B85321A2502X160 B85321A2502Y160 B85321A2502Z160 B85321A2502W160

Approvals
x = Approval granted

Insertion loss dB typical values at 50

CR µF 2 x
10 kHz
100 kHz
1 MHz
10 MHz 25
100 MHz 1 GHz

Dimensional drawings Figure 1, B85321A2502X160

Please read Cautions and warnings and Important notes at the end of this document.

Thread

Tightening torque

M10 x 3 Nm

General tolerances according to ISO Dimensions in mm

Page 3 of 12

Feedthrough components Filters

Figure 2, B85321A2502Y160

B85321A*160 16 mm, 16 A

Figure 3, B85321A2502Z160

Tightening torque 3 Nm

General tolerances according to ISO Dimensions in mm

Figure 4, B85321A2502W160

Tightening torque 3 Nm

General tolerances according to ISO Dimensions in mm

Please read Cautions and warnings and Important notes at the end of this document.

Tightening torque 3 Nm General tolerances according to ISO

Dimensions in mm

Page 4 of 12

Feedthrough components Filters

B85321A*A250, A750 30 mm, 25 A, 75 A

Feedthrough filters 30 mm Technical data and measuring conditions

Rated voltage VR Rated current IR

Capacitance tolerance Climatic category IEC 60068-1 Screw cap fixing Appprovals
250 V AC 50/60 Hz / 500 V DC and 600 V DC Referred to 40 °C rated temperature Reduced current values at 400 Hz ±20% 40/085/56 °C/+85 °C/56 days damp heat test M20 x 1 UL 1283, 250 V AC and CSA C22.2 No.8, 250 V AC
Characteristics and ordering codes

IR CR

A µF

VR = 250 V AC
25 2 x 600 25 2 x 600 25 2 x 500 75 2 x 600 75 2 x 600 75 2 x 500

Vtest DC V
3000 2000 1700 3000 2000 1700

Terminal
x = Approval granted
Approx. weight Ordering code g

B85321A2204A250

B85321A2105A250

B85321A2205A250

B85321A2204A750

B85321A2105A750

B85321A2205A750

Approvals

Insertion loss dB typical values at 50

CR µF 2 x 2 x 2 x
10 kHz 2 5
100 kHz 10 25 30
1 MHz 25 45 60
10 MHz 70 80 90
100 MHz > 100 > 100 > 100
1 GHz > 100 > 100 > 100

Dimensional drawing

Please read Cautions and warnings and Important notes at the end of this document.

Thread M6 M20 x 1

Tightening torque 3 Nm
10 +1 Nm

General tolerances according to ISO Dimensions in mm

Page 5 of 12

Feedthrough components Filters

B85321A*A630, A101 A501 55 mm, 63 A 500 A

Feedthrough filters 55 mm Technical data and measuring conditions

Rated voltage VR Rated current IR

Capacitance tolerance Climatic category IEC 60068-1 Screw cap fixing Approvals
250 V AC 50/60 Hz / 350 V DC and 600 V DC Referred to 40 °C rated temperature Reduced current values at 400 Hz ±20% 40/085/56 °C/+85 °C/56 days damp heat test M32 x UL 1283, 250 V AC
Characteristics and ordering codes

Vtest Terminal Dimensions
l+1 l1-1 l2-3

VR = 250 V AC, IR = 63 A
2 x 600 3000 M6 2 x 600 2500 M6 2 x 600 2500 M6 2 x 350 1700 M6
100 166 45 100 166 45 100 166 45 100 166 45

VR = 250 V AC, IR = 100 A
2 x 600 3000 M8 2 x 600 2500 M8 2 x 600 2500 M8 2 x 350 1700 M8
100 180 52 100 180 52 100 180 52 100 180 52

VR = 250 V AC, IR = 200 A
2 x 600 3000 M10 2 x 600 2500 M10 2 x 600 2500 M10 2 x 350 1700 M10
100 185 55 100 185 55 100 185 55 100 185 55

VR = 250 V AC, IR = 300 A
2 x 600 3000 M12 2 x 600 2500 M12 2 x 600 2500 M12 2 x 350 1700 M12
100 195 60 100 195 60 100 195 60 100 195 60

VR = 250 V AC, IR = 400 A
2 x 600 3000 M16 2 x 600 2500 M16 2 x 600 2500 M16 2 x 350 1650 M16
130 245 72 130 245 72 130 245 72 130 245 72

Approx. weight g
1250
Ordering code

B85321A2105A630 B85321A2205A630 B85321A2405A630 B85321A2945A630

B85321A2105A101 B85321A2205A101 B85321A2405A101 B85321A2945A101

B85321A2105A201 B85321A2205A201 B85321A2405A201 B85321A2945A201

B85321A2105A301 B85321A2205A301 B85321A2405A301 B85321A2945A301

B85321A2105A401 B85321A2205A401 B85321A2405A401 B85321A2945A401
x = Approval granted

Approvals

Please read Cautions and warnings and Important notes at the end of this document.

Page 6 of 12

Feedthrough components Filters

B85321A*A630, A101 A501 55 mm, 63 A 500 A

Vtest Terminal Dimensions
l+1 l1-1 l2-3

VR = 250 V AC, IR = 500 A
2 x 600 3000 M18 2 x 600 2500 M18 2 x 600 2500 M18 2 x 350 1650 M18
130 250 75 130 250 75 130 250 75 130 250 75

Approx. weight g
1400
Ordering code

B85321A2105A501 B85321A2205A501 B85321A2405A501 B85321A2945A501
x = Approval granted

Approvals

Insertion loss dB typical values at 50

CR µF 2 x 2 x 2 x 2 x
10 kHz 5
10 15 25
100 kHz 25 30 35 40
1 MHz 45 60 70 90
10 MHz 80 > 100 > 100 > 100
100 MHz > 100 > 100 > 100 > 100
1 GHz > 100 > 100 > 100 > 100

Dimensional drawing

Thread M6 M8 M10 M12 M16 M18

Tightening torque 3 Nm 5 Nm 8 +2 Nm
12 +2 Nm 28 +2 Nm 35 +2 Nm

Please read Cautions and warnings and Important notes at the end of this document.

General tolerances according to ISO Dimensions in mm

Thread M32 x

Tightening torque 24 Nm

Page 7 of 12

Feedthrough components Filters

B85321

Cautions and warnings

Please read all safety and warning notes carefully before installing the EMC filter and putting it into operation see The same applies to the warning signs on the filter. Please ensure that the signs are not removed nor their legibility impaired by external influences.

Death, serious bodily injury and substantial material damage to equipment may occur if the appropriate safety measures are not carried out or the warnings in the text are not observed.

Using according to the terms

The EMC filters may be used only for their intended application within the specified values in lowvoltage networks in compliance with the instructions given in the data sheets and the data book. The conditions at the place of application must comply with all specifications for the filter used.

Warning It shall be ensured that only qualified persons electricity specialists are engaged on work such as planning, assembly, installation, operation, repair and maintenance. They must be provided with the corresponding documentation.

Danger of electric shock. EMC filters contain components that store an electric charge. Dangerous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off.

The protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective-earth connection must be observed.

Impermissible overloading of the EMC filter or filter, such as with circuits able to cause resonances, impermissible voltages at higher frequencies etc. can lead to bodily injury and death as well as cause substantial material damages e.g. destruction of the filter housing .

EMC filters and filters must be protected in the application against impermissible exceeding of the rated currents by overcurrent protective circuitry.

In case of leakage currents mA you shall mount the PE conductor stationary with the required cross section before beginning of operation and save it against disconnecting. For leakage currents IL1 <10 mA the PE conductor must have a KU value2 of A3 for leakage currents IL mA the PE conductor must have a KU value of Output chokes and output filters must be protected in the application against impermissible exceeding of the component temperature. The converter output frequency must be within the specified range to avoid resonances and uncontrolled warming of the output chokes and output filters.
1 IL = leakage current let-go 2 The KU value symbol KU is a classification parameter of safety-referred failure types designed to ensure protection against hazardous
body currents and excessive heating.
3 A value of KU = with respect to interruptions is attained with a permanently connected protective earth circuit mm2 connected via shroud connectors IEC and b a protective earth circuit.
4 KU = 6 with respect to interruptions is achieved for lines mm2 where the type of connection and line layout correspond to the requirements for PEN conductors as specified in relevant standards.

Please read Cautions and warnings and Important notes at the end of this document.

Page 8 of 12
Display of ordering codes for EPCOS products
The ordering code for one and the same product can be represented differently in data sheets, data books, other publications and the website of EPCOS, or in order-related documents such as shipping notes, order confirmations and product labels. The varying representations of the ordering codes are due to different processes employed and do not affect the specifications of the respective products. Detailed information can be found on the Internet under

Please read Cautions and warnings and Important notes at the end of this document.

Page 10 of 12

Feedthrough components Filters

B85321

Symbols and terms

Symbol English
α CR CX CY dv/dt
fM fP fR fres IC ILK Imax IN Iop Ipk Iq IR IS L

LR Lstray PL R

Ris Rtyp TA Tmax Tmin TR uk Veff VK VLE VN VR Vpeak Vtest VX VY XL Z

Insertion loss Rated capacitance X capacitor Capacitance Y capacitor Voltage drop input to output Rate of voltage rise Frequency Converter output frequency Pulse frequency Rated frequency Resonant frequency Current through capacitor Filter leakage current Maximum current Nominal current Operating current design current Rated peak withstand current Capacitive reactive current Rated current Interference current Inductance Rated inductance Stray inductance Power loss Resistance Insulation resistance DC resistance, typical value Ambient temperature Upper category temperature Lower category temperature Rated temperature Refered voltage drop in % RMS voltage drop Voltage line to earth voltage line to ground Nominal voltage Rated voltage Peak voltage Test voltage over X capacitor Voltage over Y capacitor Inductive reactance Impedance, absolute value

German

Einfügungsdämpfung Bemessungskapazität Kapazität X-Kondensator Kapazität Y-Kondensator Spannungsabfall im Filter Spannungsanstiegsgeschwindigkeit Frequenz Motorfrequenz Pulsfrequenz Bemessungsfrequenz Resonanzfrequenz Strom durch Kondensator Filter-Ableitstrom Maximalstrom Nennstrom Betriebsstrom Bemessungs-Stoßstromfestigkeit Kapazitiver Blindstrom Bemessungsstrom Störstrom Induktivität Bemessungsinduktivität Streuinduktivität Verlustleistung Widerstand Isolationswiderstand Gleichstromwiderstand, Richtwert Umgebungstemperatur Obere Kategorietemperatur Untere Kategorietemperatur Bemessungstemperatur Bezogener Spannungsabfall in % Effektivspannung Spannungsabfall Spannung Phase zu Erdpotential Nennspannung Bemessungsspannung Spitzenspannung Prüfspannung Spannung über X-Kondensator Spannung über Y-Kondensator Induktiver Blindwiderstand Scheinwidertand Scheinwiderstand Betragswert

Please read Cautions and warnings and Important notes at the end of this document.

Page 11 of 12

Important notes

The following applies to all products named in this publication:

Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application.

We also point out that in individual cases, a malfunction of electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of an electronic component could endanger human life or health e.g. in accident prevention or lifesaving systems , it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer e.g. installation of protective circuitry or redundancy that no injury or damage is sustained by third parties in the event of malfunction or failure of an electronic component.

The warnings, cautions and product-specific notes must be observed. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions e.g. because they are classed as hazardous . Useful information on this will be found in our Material Data Sheets on the Internet Should you have any more detailed questions, please contact our sales offices. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. The aforementioned does not apply in the case of individual agreements deviating from the foregoing for customer-specific products. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the "General Terms of Delivery for Products and Services in the Electrical Industry" published by the German Electrical and Electronics Industry Association ZVEI . The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CeraLink, CeraPlas, CSMP, CSSP, CTVS, DeltaCap, DigiSiMic, DSSP, FilterCap, FormFit, MiniBlue, MiniCell, MKD, MKK, MLSC, MotorCap, PCC, PhaseCap, PhaseCube, PhaseMod, PhiCap, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SiMic, SIMID, SineFormer, SIOV, SIP5D, SIP5K, TFAP, ThermoFuse, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at

Page 12 of 12
More datasheets: DK194P | QTLP670CYTR | QTLP670CIWTR | QTLP670CIGTR | QTLP670CSTR | QTLP670CRTR | 44214 | EA-XPR-001 | AIMB-567G2-00A1E | AIMB-567VG-00A1E


Notice: we do not provide any warranties that information, datasheets, application notes, circuit diagrams, or software stored on this website are up-to-date or error free. The archived B85321-A2405-A630 Datasheet file may be downloaded here without warranties.

Datasheet ID: B85321-A2405-A630 511712