1180-02-0.5A-MK

1180-02-0.5A-MK Datasheet


Type No. 1180 single pole thermal circuit breaker, plug-in mounting

Part Datasheet
1180-02-0.5A-MK 1180-02-0.5A-MK 1180-02-0.5A-MK (pdf)
Related Parts Information
1180-02-4A-MK 1180-02-4A-MK 1180-02-4A-MK
1180-02-8A-MK 1180-02-8A-MK 1180-02-8A-MK
1180-02-5A-MK 1180-02-5A-MK 1180-02-5A-MK
1180-02-3A-MK 1180-02-3A-MK 1180-02-3A-MK
1180-02-2A-MK 1180-02-2A-MK 1180-02-2A-MK
1180-02-2.5A-MK 1180-02-2.5A-MK 1180-02-2.5A-MK
1180-02-1.5A-MK 1180-02-1.5A-MK 1180-02-1.5A-MK
1180-02-10A-MK 1180-02-10A-MK 1180-02-10A-MK
1180-02-1A-MK 1180-02-1A-MK 1180-02-1A-MK
1180-02-6A-MK 1180-02-6A-MK 1180-02-6A-MK
PDF Datasheet Preview
Thermal Overcurrent Circuit Breaker

Miniaturised single pole thermal circuit breaker with switching function optional push-push actuation . Reliable snap-acting and trip-free mechanism. Approved to CBE standard EN/IEC S-type, TO. Blade terminals fitting into sockets for rail mounting.

Protection of loads in power distribution systems in control cabinets and process control.
Ordering information

Type No. 1180 single pole thermal circuit breaker, plug-in mounting

Versions 01 with switching function, without label 02 reset function only, without label Current rating range A
1180 - 01 - 1 A ordering example

Preferred types

Preferred types 1180-01-

Standard current ratings A 1 2 3 4 5 6 8 10

Standard current ratings and typical internal resistance values

Current rating A 1

Internal

Current
resistance Ω rating A

Internal resistance Ω

Technical data

Voltage rating Current ratings Typical life Ambient temperature Insulation co-ordination IEC 60664 and 60664 A Dielectric strength IEC 60664 and 60664A
operating area installation area Insulation resistance Interrupting capacity Icn Interrupting capacity UL 1077 Degree of protection IEC 60529/DIN 40050 Vibration without terminal block

Shock without terminal block Corrosion

Humidity

Mass

AC 250 V DC 65 V UL, UL Canada AC 250 V DC 72 V
6,000 operations at 1 x IN low-inductance 3,000 operations at 1 x IN inductive 500 operations at 2 x IN inductive
°C T 60 °F
rated impulse
pollution
withstand voltage degree
reinforced insulation in operating area
test voltage AC 3,000 V AC 1,500 V
> 100 MΩ DC 500 V

AC 250 V DC 72 V
6 x IN 8 x IN 25 x IN 10 x IN 20 x IN
2,000 A
2,000 A

AC 250 V, DC 65 V AC 250 V, DC 65 V DC 30 V DC 30 V DC 30 V
operating area IP40 terminal area IP00
5 g 57-500 Hz ± mm 10-57 Hz to IEC 60068-2-6, test Fc, 10 frequency cycles/axis and to EN 50155
25 g 11 ms to IEC 60068-2-27, test Ea
96 hours at 5 % salt mist, to IEC 60068-2-11, test Ka
240 hours at 95 % RH to IEC 60068-2-78, test Cab
approx. 15 g

Approvals

Authority Standard

Rated voltage

Current ratings

IEC/EN
All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted.