CliQ DIN Rail Power Supply 24V 480W 3Phase

Model No. DRP 024V 480W 3AA

Weight 1.71KG

Size:
121 mm X 160 mm X mm H x W x D

RoHS Compliant Over load protection Over voltage protection Over temperature protection Expected life time 10 Years Power boost 150% for 3 seconds Compact design for easy handling Output terminals for fast wiring and easy installation With Conformal Coating Class 1 Div 2 Hazard Loc Redundancy DRR-20A & DRR-40A or External ORing Diode

The new CliQ DRP024V480W3AA is the latest offering from one of the World’s No.1 Power Supply Company. The product offers a nominal output voltage of 24V, a wide temperature range from -20°C to 75°C and a minimum holdup time of >25ms.The state-of-the-art design is made to withstand harsh industrial environments. The rugged, compact design aluminium case is shock and vibration resistant according to IEC60068-2-6. The 480 watts CliQ DIN Rail power supply provides over voltage, overload and thermal protection. Due to the wide input voltage range from 320 to 575 Vac, the Delta’s CliQ power supply is worldwide usable, multiple output terminals for fast wiring and easy installation.

INPUT SPECIFICATION

Input Voltage Nominal Input Voltage range Input Frequency Nominal Input Frequency range DC Input Voltage Nominal DC Input Voltage Range Input Current Efficiency Inrush current Cold Start Leakage Current Power Factor
400-500Vac 320-575Vac 50 - 60Hz 47 - 63Hz 565-700Vdc 450-800Vdc < 1.60A 400Vac , <1.10A 500Vac > 3 x 400Vac & 3 x 500Vac <50A 3 x400Vac & 3 x 500Vac < 3.5mA 500Vac Conform to EN61000-3-2

OUTPUT SPECIFICATION

Output Voltage Nominal Output Voltage Tolerance Output Voltage Adjust Range Line Regulation Load Regulation Residual Ripple PARD , 20MHz BW Output Current Nominal Power Derating above 50°C Rise Time Start-Up Time Hold-Up Time Dynamic Response Overshoot & Undershoot O/P Voltage Startup with capacitive loads
24 Vdc +/- 2% Initial set point tolerance 22 28 Vdc < Typical 320 to 575Vac input, 100% load < 1% Typical 320 to 575Vac input, 0 to 100% load < 50mVpp / <240mVpp 25°C 20.0A Derated Linearly / °C < 100ms nominal input, 100% load 25°C < 1000ms nominal input, 100% load 25°C > 25ms 3 x 400Vac, > 50ms 3 x 500Vac 100% load, 25°C +/-5% 0% - 100% load
10,000µF nominal input & nominal O/P voltage 24V 25°C

CliQ DIN Rail Power Supply 24V 480W 3Phase

Device Description:
1 Input terminal block connector 2 Output terminal block connector 3 DC voltage adjustment potentiometer 4 DC OK control LED green 5 Universal mounting rail system

Mechanical Drawing:

MECHANICAL SPECIFICATION

Dimension Weight Cooling System Input Terminal Output Terminal Output Indicator Casing
121 mm X 160 mm X mm H x W x D 1.71kg Convection Terminal Block with screw M4x4 pins rated 600V/20A Terminal Block with screw M4x4 pins rated 600V/20A Green LED DC OK Aluminum

CliQ DIN Rail Power Supply 24V 480W 3Phase

Block Diagram:

CliQ DIN Rail Power Supply 24V 480W 3Phase

PROTECTION

Over Voltage Protection Over Load, Over Current Protection Over Temperature Protection Short Circuit Protection
32V +10%/-10%, SELV output, Hicc-up Mode, Non-Latching Auto recovery . > 150% of rated load current, Hicc-up Mode, Non-Latching Auto recovery . < 80°C Ambient 100% load. Non-Latching Autorecovery . Hicc-up Mode, Non-Latching, Auto-recovery when the fault is removed .

Over Load Protection

The Power Supply is provided with an overload protection OLP/OCP function which protects the power supply from possible damage by over current. Additionally power supply also has over temperature protection OTP in case the over load condition persists for a longer duration and is below the overload trigger point but > 100% load. Typically the over load current IOL is > ISURGE 150% output voltage will start drooping down when the power supply reaches max power limit and will run into bouncing mode when the output reaches UVLO under voltage point . The output voltage will recover automatically when the overload condition is removed.

Over Temperature Protection

Additionally power supply also has over temperature protection OTP as mentioned above this OTP comes into picture when the over load condition persists for a longer duration and the output current level is below the overload trigger point but > 100% load.Also in the event of a higher ambient operating condition with 100% load the power supply will run into OTP when the Ambient temperature is > 80°C. The protection is self recoverable when activated output voltage bounces until the operating ambient temperature of the power supply is reduced or the power supply is used within its power derating curve.

Over Voltage Protection

The Power Supply is protected by Over voltage in the event that power supply feedback circuit fails the output voltage will not be >32V +10%/-10%,under any Line/Load and operating ambient conditions. The unique feature about this over voltage protection OVP is that power supply doesn’t shut down but goes in 2nd level regulation which is 30-32Vdc. The Power supply will continue to deliver the power but due to high output voltage it will be operating > 100% load 32V x 20A = 640Watts if this condition persists the power supply will sense OTP Over Temperature Protection and will go under bouncing mode. The power supply output voltage will recover back to 24Vdc once the fault condition is removed.

Short Circuit Protection

The Power Supply also has a short circuit protection which is in line with the overload protection and activates whenever there is a short across the output voltage, output goes in bouncing mode and remains until the fault is removed.

CliQ DIN Rail Power Supply 24V 480W 3Phase

Derating Curve

Note

Do not use the device in areas outside of the shaded portion shown in the above graph. Internal parts may gradually deteriorate and become damaged.

For the power derating refer above graph ambient temperature > 50°C, the output capacity has to be reduced by per Celsius increase in temperature. If the output capacity is not reduced when Amb > 50°C device will run into thermal protection by switching off i.e. device will go in bouncing mode and will recover when Amb is lowered or load is reduced as far as necessary to keep device in working condition.

If the device has to be mounted in any other direction, please contact your service provider for more details. In order for the device to function in the manner intended, it is also necessary to observe a lateral spacing of