84872023

84872023 Datasheet


EUL/EUH AC/DC voltage control EUH Part number 84872033

Part Datasheet
84872023 84872023 84872023 (pdf)
Related Parts Information
84872031 84872031 84872031
84872030 84872030 84872030
84872034 84872034 84872034
84872021 84872021 84872021
84872024 84872024 84872024
84872020 84872020 84872020
84872033 84872033 84872033
PDF Datasheet Preview
22/10/2012

EUL/EUH AC/DC voltage control EUH Part number 84872033

Voltage monitoring 2 relays to cover 6 ranges of measurement 0.2V to 600V Automatic recognition AC/DC Frequency up to 500 Hz

Part numbers

Type 84 872 020 EUL 84 872 021 EUL 84 872 023 EUL 84 872 024 EUL 84 872 030 EUH 84 872 031 EUH 84 872 033 EUH 84 872 034 EUH

Measurement range 0,2 V 0,2 V 0,2 V 0,2 V 15 V 15 V 15 V 15 V

Specifications

Supply voltage Un Operating range Maximum power consumption Frequency of measured signal Threshold Ue Hysteresis Display precision Delay on thresold crossing Tt Output relay Temperature Use °C Storage temperature 0C
0,85 1,15 Un 3 VA / 1 W 40 500 Hz Adjustment from 10 to 100 % of the measurement range Adjustment from 5 to 50 % of the displayed threshold ± 10 % of the full scale 0,1 3 s ±10 % 1 AgNi changeover, 8 A max -20 -30

Inputs Sensitivity

Input resistance

E1-M 15 to 150V E2-M 30 to 300V E3-M 60 to 600V

E1-M 100kΩ E2-M 300kΩ E3-M 600kΩ

Principles

Supply voltage 24 V DC 24 V AC 120 V AC 230 V AC 24 V DC 24 V AC 120 V AC 230 V AC

Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012

When the value of the controlled voltage, AC or DC, reaches the treshold Ue displayed on the front face, the output relay changes state at the end of a time delay T1, which can be set on the front face at between and 3s. Once the voltage drops below 5 to 50 % of the treshold hysteresis , the output relay changes state again instantly. Changing the hysteresis onthe front face does not therefore modify the value of the preset treshold.

Legend

Treshold Ue

Hysteresis

UPPER function

UNDER function

Unit power-up

Controlled voltage
*** TRADUCTION MANQUANTE ***

Principles

When the value of the controlled voltage, AC or DC, reaches the treshold Ue displayed on the front face, the output relay changes state at the end of a time delay T1, which can be set on the front face at between and 3s and remains latched in this position.

Legend

Treshold Ue

Hysteresis

UPPER function

Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012

Dimensions mm EUL / EUH

UNDER function Unit power-up Controlled voltage

Connections CA EUHDU_C01

Connections CA EULH_C01

Legend *** TRADUCTION MANQUANTE ***

Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
22/10/2012
More datasheets: 162C18709X | 132A15019X | 3553 | B000002 | 1802 | DM74ALS125N | DM74ALS125M | DM74ALS125MX | 84872031 | 84872030


Notice: we do not provide any warranties that information, datasheets, application notes, circuit diagrams, or software stored on this website are up-to-date or error free. The archived 84872023 Datasheet file may be downloaded here without warranties.

Datasheet ID: 84872023 507088