Isolates, amplifies, linearizes, & protects analog input voltages from a wide variety of two-, three- and four-wire Resistor Temperature Detectors RTDs . Module provides a constant +10V bridge excitation voltage. Module provides simultaneous precision voltage and current outputs linear to input temperature. RTD excitation current and three-wire lead resistance compensation provide a complete signal conditioning solution. Module circuitry can withstand 220v rms at the input screwterminals. All 3B34 series modules are mix-and-match and Hot Swappable.

Part Datasheet
3B34-CUSTOM 3B34-CUSTOM 3B34-CUSTOM (pdf)
PDF Datasheet Preview
Isolates, amplifies, linearizes, & protects analog input voltages from a wide variety of two-, three- and four-wire Resistor Temperature Detectors RTDs . Module provides a constant +10V bridge excitation voltage. Module provides simultaneous precision voltage and current outputs linear to input temperature. RTD excitation current and three-wire lead resistance compensation provide a complete signal conditioning solution. Module circuitry can withstand 220v rms at the input screwterminals. All 3B34 series modules are mix-and-match and Hot Swappable.

Industrial signal conditioning Industrial signal isolation Industrial signal filtering

PRODUCT OVERVIEW

The 3B Series of Signal Conditioning I/o Subsystems provide a low-cost, versatile method of transferring analog transducer signals to a data acquisition, monitoring or control system without the inherent noise, non-linearity, drift and extraneous voltages. The modules are designed to directly accept analog signals from Thermocouples, RTD’s, AC and DC Strain Gages, Torque Transducers, Frequency Transducers, LVDTs, millivolt or process current signals. The modules amplify, isolate, linearize and convert the transducer output signals to standardized analog inputs for high-level analog I/O subsystems. The 3B Series Subsystem consists of a 10” relay rack with universal mounting backplane and a family of plug-in up to 16 per rack input and output signal conditioning modules.

Eight and four channel backplanes are also available. Each backplane incorporates screw terminals for sensor inputs and current outputs and a 26-pin connector for high-level singleended voltage outputs to the user’s equipment.

The input modules feature complete signal conditioning circuitry optimized for specific sensors or analog signals and provide two simultaneous high-level analog outputs 0 to +10V or +10V and 4-20 mA or 0-20 mA .

Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties that may result from its use. Specifications subject to change without notice. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices. Trademarks and registered trademarks are the property of their respective companies.

Isolated, Linearized RTD Input 3B34

FUNCTIONAL BLOCK DIAGRAM

Figure 3B34 Functional Block Diagram

Output modules accept 0 to +10V or +10V single-ended signals and provide an isolated 4-20 mA or 0-20 mA process signal. All modules feature a universal pin-out and may be readily hot-swapped under full power and interchanged without disrupting field wiring.

The Analog Devices 3B Series Signal Conditioning Subsystem is designed to easily handle signal conditioning problems in measurement and control applications. Some typical uses are in microcomputer-based data acquisition systems, programmable controllers, analog recorders, dedicated control systems, and any other applications where monitoring of temperature, pressure, flow and analog signals are required. Since each input module features two simultaneous outputs, the voltage output can be used to provide an input to a microprocessor-based data acquisition or control system while the current output can be used for analog transmission, operator interface, or an analog backup system.

Each input module is a single-channel signal conditioner which plugs into a socket on the backplane and accepts its signal from the input screw terminals. All input modules provide input protection, amplification and filtering of the input signal, accuracy of low drift of +1 uV/oC low-level input modules , and feature two high-level analog outputs that are compatible with most process instrumentation. The isolated input modules also provide +1500 V peak isolation.

The choice of a specific 3B module depends upon the type of input signal. Input modules are available to accept millivolt, volt, process current, thermocouple, RTD, AC and DC strain gage, frequency and LVDT inputs. The voltage output of each module is available from the sysem I/O connector while the current output is available on the output screw terminals.

One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.

Tel:

Fax 2004 Analog Devices, Inc. All rights reserved.

The 3B34 is a single-channel signal conditioning module which amplifies, protects, filters, linearizes, and isolates analog input voltages from a wide variety of two-, three-, and four-wire Resistor Temperature Detectors RTDs , providing simultaneous precision voltage and current outputs, linear to input temperature. RTD excitation current and three-wire lead resistance compensation provide a complete signal conditioning solution. The 3B34 protects its computer side outputs from damage and loss of signal integrity by isolating them up to +1500V peak and shielding its input and excitation circuit from damage from field-side over-voltage faults up to 220V rms. The current output withstands 130V rms without damage and interfaces to user equipment through screw terminals on the 3B Series backplane. The 3B34 is a plug-in, mix-and-match, hotswappable module, easily field calibrated via front-panel zero and span adjustments for both voltage and current outputs.
3B Series Custom-Ranging Program Externallyprogrammable Model 3B34-00, enables the user to configure a special input range by using the optional plug-on AC1310 ranging card, which houses user-supplied resistors to determine zero and span. To facilitate selecting resistors, a Windows program, 3B-CUSTOM, calculates resistor values based on the user-desired input/output ranges.
3B34

A differential chopper-stabilized low-drift input amplifier provides stable gain and long-term stability. This enables the use of very low RTD excitation current to minimize self-heating and preserve measurement accuracy. A 250 uA excitation current for platinum and nickel RTDs and a 1mA excitation current for copper RTDs is provided to create an input voltage to the 3B34. For three-wire RTDs, the excitation current flows through the third RTD lead to eliminate the effect of lead resistance with an accuracy of +0.02oC/W. Internal multi-pole low-pass filtering with a 3-Hz cutoff -3dB enhances normalmode and common-mode ejection at 50/60 Hz, enabling accurate measurement of small signals in high electrical noise. The differential input circuit on the field side is fully floating, eliminating the need for any input grounding. Signal isolation is accomplished by transformer coupling using a proprietary modulation technique for linear, stable and reliable performance. A demodulator on the computer side of the signal transformer recovers the original signal, which is then filtered and buffered to provide a low-noise, low-impedance output voltage this output also drives a voltage-to-current converter to provide a simultaneous current output for interfacing versatility.

Figure 2
3B34
3B34 Models Available

Model 3B34-00

RTD Sensor 2,3, or 4-wire
100 Pt, alpha =

Input Range Externally Programmable 2
3B34-01
100 Pt, alpha =
-100°C to +100°C
3B34-02
100 Pt, alpha =
0°C to +100°C
3B34-03
100 Pt, alpha =
0°C to +200°C
3B34-04
100 Pt, alpha =
0°C to +600°C
3B34-Custom